ZG-106

CO2 Monitor (Model : ZG106)
ZG 106 is a portable & accurate handheld C02 Monitor
Which can be put on desktop It measures the Co2 concentration and ambient temperature. It uses NDIR technology to ensure long term stability -Build-in several modes help you understand ambient air quality.
single-gas-detector

Request a quote
Specifications :

  • Method – NDIR
    Display – LCD
    Independent CO2 and Temperature readings.
    Calculates and Displays Ventilation Rates
    Sample Method – Diffusion or flow through (50-200
    ml/min)
  • Performance – CO2 Channel
    Measurement Range : 0-3000 ppm display
    Display Resolution :

    • 1ppm at 0-1000 ppm
    • 5 ppm at 1000-2000 ppm
    • 10 ppm at 2000 – 3000 ppm

    Accuracy : ±50 ppm or ±5% of reading
    Repeatability : ±20 ppm
    Temperature Dependance : ±0.1% of resding per 0C
    or ±2 ppm per 0C whichever is greater refrenced to 2500
    Pressure Dependance : 0.13% of reading per mm Hg (Corrected via user input for attitude)
    Response Time : <4 min for 63% of step change
    Warm-Up Time : <50 seconds at 220C
    Calibration Interval : 12 months, offset adjustment using single gas at 0-1000 ppm CO. Full factory calibration available.

  • Performance – Temperature Channel
    Temperature Range : Display 32 to 122 0F (0 to 500C)
    Display Resolution : 0.1 0F (0.10C)
    Display Options : 0F 0C or Off. Set with Up, Down button
    Accuracy : ±2 0F (±10C)
    Response Time : 20-30 minutes
    Calibration interval : 12 months
  • Outputs
    OC : Normally Low, 100mA max. @24VAC, Adjustable set point, factory settings is 1000 ppm, hysteresis is 50 ppm
    One RJ-45 Connector digital output in RII protocol
    One Graphing Software ZyAura View (Under developing)
  • Power Supply Battery TypeTwo power supply types
    Battery type : Alkaline, AA* 4(80 hours)
    External : 6 VDC from external AC/DC adapter which is included in package (Use specified AC adaptor only)Power Requirement
    160 mA Peak, 15 mA average from 6V
  • General Operating ConditionsOperating Temperatures :
    32-1220F (0-500C) 0-95% RH, non-condensing
    Storage Temperatures : -4 to 140 0F (-20 to 600C)
Power Button Enter Button Down Button
Up Button Model Button LCD Display
LED Light Function Label Gas Entry Hole
Power inlet Rj45 socket Housing Stand
Battery Cover AA Batteries *4

Safety(?) News