CASPER – 2 & 3 CELLS COMBUSTION ANALYZER

MAIN FEATURES:
  • Standard Version With 2 Cells For 02 And Co (H2 Immunity)
  • Optional 3Rd Cell For No
  • Pre-Calibrated Gas Sensors, Field Replaceable
  • Flue Gas And Outdoor Air Temperature Measurement
  • Draft And Differential Pressure Measurement
  • Boiler (Condensing Also ) Efficiency Calculation
  • CO2, Heat Stack Loss, Excess Air Calculation
  • Ambient Co And No Measurement
  • Ir Output For Remote Thermal Printer
  • Optional Bluetooth Communication
  • Mini Usb Output
  • Big Blue (38 X 70 Mm ) Graphic LCD Backlight
  • Keypad In Silicone Rubber
  • Rechargeable Lithium Ions Batteries
  • External Charger/Power Supply With Ac Plug
  • 300 Tests Internal Memory
  • Software And USB Cable Unlimited Data Storage On Pc
  • Self Diagnostic Function With Exhausted Gas Sensors Alarms
  • 180,300 And 700 Mm Flue Gas Sampling Probes
  • 220 Mm Flexible Flue Gas Sapmpling Probe
  • External Condensation Trap And Dust Filter
  • Up To 16 Pre-Programmed Fuels, Including Pellets And Wood
  • 5 Languages Pre-Programmed
  • User Manuals And Calibration Certificate
  • Dimensions 220 X 110 X 55 Mm, Weight 0,55 Kg
  • TUV certified
single-gas-detector

Request a quote
CASPER :

MEASUREMENT SENSOR RANGE RESOLUTION ACCURACY
O2 Electrochemical sensor 0.. 25.0% vol. 0.1% vol ± 0.2% vol.
CO with low
sensitivity to H2
Electrochemical sensor 0.. 8000 ppm 1 ppm ±20 ppm 0.. 400 ppm ±5%
measured value 201.. 4000 ppm ±10% measured value 4001..8000ppm
NO Electrochemical sensor 0.. 5000 ppm 1 ppm ±5 ppm 0.. 100 ppm ±5%
measured value 101..5000ppm
Nox calculated
CO2 calculated 0.. 99.9% vol. 0.1% vol.
Air temperature Pt100 sensor -20.0… 120 °C 0.1 °C ± 0.5%
Flue Gas Temperature TcK sensor -100.0 .. 1250.0°C 0.1 °C ±0.5 °C 0..
100 °C ±0.5% measured value 101.. 1250 °C
Pressure (draught &
differential )
Piezoelectric sensor -10… 200.00 hPa 0.01 hPa ±1% measured value
-10.00..-2.01 hPa ±2 Pa -200 .. 200Pa ±1% measured value
2.01… 200.00hPa
Differential
temperature
calculated 0.. 1250.0 °C 0.1 °C
Air Index calculated 0.00.. 9.50 0.01
Excess Air calculated 0..850% 1%
Stack loss calculated 0.0.. 100.0% 0.1%
Efficiency calculated 0.0.. 100.0% 0.1%
Efficiency
(condensing)
calculated 0.0.. 120.0 % 0.1%
Smoke
Index
External
instrument
0.. 9

Safety(?) News